CONSTRUCTION CODE APPEALS COMMITTEE
AGENDA
MARCH 31, 2015 - 9:00 A.M.
CITY HALL CONFERENCE ROOM
15 LOOCKERMAN PLAZA
DOVER, DELAWARE
PUBLIC COMMENTS ARE WELCOMED ON ANY ITEM AND WILL BE PERMITTED AT APPROPRIATE TIMES. WHEN
POSSIBLE, PLEASE NOTIFY THE CITY CLERK (736-7008 OR E-MAIL AT CITYCLERK@DOVER.DE.US) SHOULD
YOU WISH TO BE RECOGNIZED.
CONSTRUCTION CODE APPEALS COMMITTEE MEMBERS
COUNCILMAN ADAM M. PERZA, CHAIR
COUNCILMAN DAVID ANDERSON
SCOTT D. KOENIG, CITY MANAGER
AGENDA ADDITIONS/DELETIONS
1. APPEAL OF REQUIREMENT FOR A COMMERCIAL KITCHEN HOOD - 147 S. GOVERNORS AVENUE
(TIFFANEE LEE-SCOTT)
2. ADJOURNMENT
/DD
S:\CLERKSOFFICE\AGENDAS&MINUTES\MISC-AGENDAS\CODE BOARD OF APPEALS\07-21-03. AGENDA.WPD
THE AGENDA ITEMS AS LISTED MAY NOT BE CONSIDERED IN SEQUENCE. THIS AGENDA IS SUBJECT TO CHANGE
TO INCLUDE THE ADDITION OR THE DELETION OF ITEMS, INCLUDING EXECUTIVE SESSIONS.
Page 2
Stein, Jody
From: Tiffanee Lee-Scott <tiffandcompany@yahoo.com>
Sent: Monday, March 02, 2015 12:47 PM
To: City Clerks Office
Subject: Ventilation Hood Appeal
Good afternoon. I am writing this letter because I am appealing the decision made by the City of
Dover to install a hood system for my commercial convection oven. I turned in a copy of the
equipment that would be in my business along with the application for my building permit on or before
June 2014. It was never once mentioned to me that I would need a hood until the day I planned on
having my grand opening on October 3, 2014. Public Health does a review of all equipment and
facilities before giving their approval, which was also turned in with my building permit. They did not
see the need for a hood system. I also had the head technical support agent for the manufacturer of
my oven send an email, which was forwarded to Tim Mullaney and Ann Marie, stating a hood was not
necessary for my oven. Apparently, that was not sufficient, so I arranged for Ann Marie and Tim to
speak with that same person directly while I listened. Bob Petrie (the same man that sent the email)
reiterated the fact that a hood was not necessary for my oven. He stated that the only thing a hood
would do would get rid of some residual heat and the smell. I'm not sure why either of those things
would be a necessity. Last Wednesday, Chris (from the city, I'm not sure his last name) came to
inspect my oven to see if a hood was necessary in his opinion. He could not even tell the oven was
on. I mention that because the oven does not let out an extensive amount of heat and the thought of
getting rid of the smell in a bakery makes no sense to me. It also seemed as if Chris was shocked to
find out that the manufacturer of the oven reported to Ann Marie and Tim that a hood was not
necessary. He had no record of that conversation ever happening. With that being said, I would just
like an appeal hearing date set so that this issue can be resolved as quickly as possible. Thank you
for your time.
Tiffanee Lee-Scott
Tiffanee & Co. Bakery
147 S Governors Ave
Dover De 19904
302-674-CAKE (office)
1
Page 3
Dover, Delaware Code of Ordinances – Part II – Code of Ordinances
Chapter 22 – Buildings and Building Regulations
Article I – In General
Sec. 22-1. - Construction code appeals committee.
(a) Established; composition; appointment. There shall be a committee to be referred to as the
"construction code appeals committee," consisting of three members, one of whom shall be the city
manager and the other two being elected city officials. The city officials shall be appointed by the city
council president at the council annual meeting.
(b) Appeals. Whenever any person is aggrieved by a decision of the building inspector with respect to
the provision of this chapter, it is the right of that person to appeal to the construction code appeals
committee. Such appeal must be filed, in writing, within 30 days after the determination by the
building inspector.
(c) Notice; hearing. Upon receipt of such an appeal, the construction code appeals committee shall set a
time and place in not less than ten, nor more than 30 days for the purpose of hearing the appeal.
Notice of the time and place of the hearing of the appeal shall be given to all parties, at which time
they may appear and be heard. The determination by the construction code appeals committee shall
be final in all cases.
(Code 1981, § 5-3; Ord. of 4-25-1994)
Page 1
Page 4
Dover, Delaware Code of Ordinances – Part II – Code of Ordinances
Chapter 22 – Buildings and Building Regulations
Article V – Mechanical Code
Sec. 22-141. - Adopted.
(a) Certain documents, three copies of which are on file in the licensing and permitting office of the city, being
marked and designated as the International Mechanical Code 2009 Edition, including appendix chapter "A",
as referenced in the building code adopted in 22-61(a), published by the International Code Council, be and
is hereby adopted as the code of the city for regulating the design, construction, quality of materials, erection,
installation, alteration, repair, location, relocation, replacement, addition to, use or maintenance of
mechanical systems in the city and providing for the issuance of permits and collection of fees therefore; and
each and all of the regulations, provisions, conditions and terms of such International Mechanical Code, as
referenced in the building code adopted in section 22-61(a), published by the International Code Council, on
file in the office of the city are hereby referred to, adopted and made a part hereof as if fully set out in this
section. The following sections of the International Mechanical Code are hereby revised:
Section 101.1 Title. Insert "City of Dover, DE" in place of "[NAME OF JURISDICTION]"
106.5 Fee Schedule. Insert "See DCO Section 22-145 Heating, air conditioning, and heat pump permit
fees" in place of "The fees for all mechanical work shall be as indicated in the following schedule:"
In place of:
Section 106.5.3 Fee refunds. Delete in its entirety.
SECTION 108 VIOLATIONS
Section 108.4 Violation Penalties. Insert "See Section 22-61(a) International Building Code Section
113.4, Violation Penalties" in place of "Any person who shall violate a provision of this code or shall fail to
comply with any of the requirements thereof or who shall erect, install, alters, or repair, a plumbing work in
violation of the approved construction documents or directive of the code official, or of a permit or certificate
issued under the provisions of this code, shall be guilty of a [SPECIFY OFFENSE], punishable by a fine of
not more than [AMOUNT], or by imprisonment not exceeding thirty (30) days, or both such fine and
imprisonment. Each day that a violation continues after due notice has been served shall be deemed a
separate offense."
Section 108.5 Stop work orders. Insert "See 22-61(a)International Building Code, Section 114.3
Unlawful continuance" in place of "Upon notice from the code official that mechanical work is being done
contrary to the provisions of this code or in a dangerous and unsafe manner such work shall immediately
cease. Such notice shall be in writing and shall be given to the owner of the property, or to the owner's agent,
or to the person doing the work. The notice shall state the conditions under which work is authorized to
resume. Where an emergency exists, the code official shall not be required to give a written notice prior to
stopping work. Any person who shall continue any work in or about the structure after having been served
with a stop work order, except such work as that person is directed to remove a violation or unsafe condition,
shall be charged with a violation of this section and shall be liable to a fine of not less than [AMOUNT] dollars
or more than [AMOUNT] dollars"
SECTION 109 MEANS OF APPEAL. Delete section in its entirety.
(b) If any section, subsection, sentence, clause or phrase of this section is, for any reason, held to be
unconstitutional, such decision shall not affect the validity of the remaining portions of this section. The city
council hereby declares that it would have passed the ordinance from which this section derives, and each
section, subsection, clause or phrase thereof, irrespective of the fact that any one (1) or more sections,
subsections, sentences, clauses and phrases be declared unconstitutional.
(Code 1981, § 5-56; Ord. of 4-9-1984, § 2; Ord. of 3-11-1991; Ord. of 4-25-1994; Ord. of 1-27-1997; Ord. of
3-13-2000; Ord. of 4-11-2005(4); Ord. of 4-14-2008; Ord. No. 2010-02, 5-10-2010)
Page 1
Page 5
DEFINITIONS
operating conditions used to move heat from one lo~ati.on to Open-spray system. A system in which a secondary cool-
another. Refrigerants are not included as heat transfer hqmds. ant is cooled or heated by the refrigerating system and then
circulated in direct contact with the air or other substance to
HEAVY-DUTY COOKING APPLIANCE. Heavy-duty be cooled or heated.
cooking appliances include electric under-fired broilers, elec-
tric chain (conveyor) broilers, gas under-fired broilers, gas Vented closed system. A system in which a secondary cool-
chain (conveyor) broilers, gas open-burner ranges (with or ant is cooled or heated by the refrigerating system and then
I
without oven), electric and gas wok ranges, and electric and gas passed through a closed circuit in the air or other substance
over-fired (upright) broilers and salamanders. to be cooled or heated, except that the evaporator or con-
denser is placed in an open or appropriately vented tank.
HIGH-PROBABILITY SYSTEMS. A refrigeration system
in which the basic design or the location of components is such INTERLOCK. A device actuated by another device with
that a leakage of refrigerant from a failed connection, seal or which it is directly associated, to govern succeeding operations
component will enter an occupancy classified area, other than of the same or allied devices. A circuit in which a given action
the machinery room. cannot occur until after one or more other actions have taken
place.
HIGH-SIDE PRESSURE. The parts of a refrigerating system
subject to condenser pressure. JOINT, FLANGED. A joint made by bolting together a pair of
flanged ends.
HOOD. An air intake device used to capture by entrapment,
impingement, adhesion or similar means, grease, moisture, JOINT, FLARED. A metal-to-metal compression joint in
heat and similar contaminants before they enter a duct system. which a conical spread is made on the end of a tube that is com-
pressed by a flare nut against a mating flare.
Type I. A kitchen hood for collecting and removing grease
vapors and smoke. Such hoods are equipped with a fire sup- JOINT, MECHANICAL. A general form of gas-tight joints
pression system. obtained by the joining of metal parts through a positive-hold-
ing mechanical construction, such as flanged joint, screwed
Type II. A general kitchen hood for collecting and remov-
joint or flared joint.
ing steam, vapor, heat, odors and products of combustion.
JOINT, PLASTIC ADHESIVE. A joint made in thermoset
HYDROGEN GENERATING APPLIANCE. A self-con-
plastic piping by the use of an adhesive substance which forms
tained package or factory-matched packages of integrated sys-
a continuous bond between the mating surfaces without dis-
tems for generating gaseous hydrogen. Hydrogen generating
solving either one of them.
appliances utilize electrolysis, reformation, chemical, or other
processes to generate hydrogen. JOINT, PLASTIC HEAT FUSION. A joint made in thermo-
plastic piping by heating the parts sufficiently to permit fusion
IGNITION SOURCE. A flame, spark or hot surface capable
of the materials when the parts are pressed together.
of igniting flammable vapors or fumes. Such sources include
appliance burners, burner ignitors and electrical switching JOINT, PLASTIC SOLVENT CEMENT. A joint made in
devices. thermoplastic piping by the use of a solvent or solvent cement
which forms a continuous bond between the mating surfaces.
IMMEDIATELY DANGEROUS TO LIFE OR HEALTH
(IDLH). The concentration of airborne contaminants that JOINT, SOLDERED. A gas-tight joint obtained by the join-
poses a threat of death, immediate or delayed permanent ing of metal parts with metallic mixtures of alloys which melt at
adverse health effects, or effects that could prevent escape from temperatures between 400°F (204°C) and l,000°F (538°C).
such an environment. This contaminant concentration level is
JOINT, WELDED. A gas-tight joint obtained by the joining
established by the National Institute of Occupational Safety
and Health (NIOSH) based on both toxicity and flammability. of metal parts in molten state.
It is generally expressed in parts per million by volume (ppm LABELED. Equipment, materials or products to which have
v/v) or milligrams per cubic meter (mg/m3). been affixed a label, seal, symbol or other identifying mark of a
INDIRECT REFRIGERATION SYSTEM. A system in nationally recognized testing laboratory, inspection agency or
which a secondary coolant cooled or heated by the refrigerat- other organization concerned with product evaluation that
maintains periodic inspection of the production of the
ing system is circulated to the air or other substance to be
above-labeled items and whose labeling indicates either.that
cooled or heated. Indirect systems are distinguished by the
the equipment, material or product meets identified standards
method of application shown below:
or has been tested and found suitable for a specified purpose.
Closed system. A system in which a secondary fluid is
either cooled or heated by the refrigerating system and then LIGHT-DUTY COOKING APPLIANCE. Light-duty cook-
ing appliances include gas and electric ovens (including stan-
circulated within a closed circuit in indirect contact with the
dard, bake, roasting, revolving, retherm, convection,
air or other substance to be cooled or heated.
combination convection/steamer, countertop conveyorized
Double-indirect open-spray system. A system in which baking/finishing, deck and pastry), electric and gas
the secondary substance for an indirect open-spray system steam-jacketed kettles, electric and gas pasta cookers, electric
is heated or cooled by an intermediate coolant circulated and gas compartment steamers (both pressure and atmo-
from a second enclosure. spheric) and electric and gas cheesemelters.
14 2009 INTERNATIONAL MECHANICAL CODE®
Page 6
EXHAUST SYSTEMS
tures are not higher than the top of the fan discharge heat or moisture and do not produce grease or smoke, except
opening. where the heat and moisture loads from such appliances are
incorporated into the HVAC system design or into the
design of a separate removal system. Typ II hoods shall be
SECTION 507 install ed above all light-duty appliances that prod uce prod-
COMMERCIAL KITCHEN HOODS ucts of combustion and do not produce grease or smoke.
507.1 General. Commercial kitchen exhaust hoods shall com- Spaces conta ining cookjng appliances that do nol require
Type II hoods shall be venlllated in accordance w!th Section
ply with the requirements of this section. Hoods shall be Type I
403.3. For lhe purpose of determining the noor area
or II and shall be designed to capture and confine cooking
requi red to be ventilated. each individual appliance that is
vapors and residues. Commercial kitchen exhaust hood sys-
tems shall operate during the cooking operation. nol requ ired lo be installed under a Ty pe lI hood shall be
con idered as occ upying not less than 100 square feet (9.3
Exceptions: m2).
1. Factory-built commercial exhaust hoods which are 507.2.3 Domestic cooking appliances used for commer-
tested in accordance with UL 710, listed, labeled and cial purposes. Domestic cooking appliances utilized for
I
installed in accordance with Section 304.1 shall not commercial purposes s hall be provided with Type I or Type
be required to comply with Sections 507.4, 507.7, II hoods as required for the type of appliances and processes
507.11 , 507.12, 507.13, 507.14 and 507.15. in accordance with Sections 507.2, 507.2.l and 507.2.2.
2. Factory-built commercial cooking recirculating sys-
507.2.4 Extra-heavy-duty. Type I hoods for use over
tems which are tested in accordance with UL 710B, extra-hea1y -d11ty cooking appliances shall not cover
listed, labeled and installed in accordance with Sec- heavy-, m dium- or light-duty appliances. Such hoods shall
tion 304 .1 shall not be required to comply with Sec- discharge lo an exhaust system that is jndepencfent of oth er
tions 507.4, 507.5, 507.7, 507.12, 507.13, 507.14 and exhaust systems.
507 .15. Spaces in which such systems are located
shall be considered to be kitchens and shall be venti- 507.3 Fuel-burning appliances. Where vented fuel-burning
lated in accordance with Table 403.3. For the purpose appliances are located in the same room or space as the hood,
of determining the floor area required to be ventilated, provisions shall be made to prevent the hood system from inter-
each individual appliance shall be considered as fering with normal operation of the appliance vents.
occupying not less than 100 square feet (9.3 m2). 507.4 Type l materials. Type 1 hood hal l be constructed of
3. Net exhaust volumes for hoods shall be permitted to steel having a min imum thickness of 0.04 66 inch (1.181 mm)
be reduced during part-load cooking conditions, (No. J8 gage) or stainless st el not less than 0.0335 inch
where engineered or listed multispeed or vari- [0.8525 mm (No. 20 MSG)] in lhicknes .
able-speed controls automatically operate the exhaust 507.5 Type II hood materials. Type II hoods shall be con-
system to maintain capture and removal of cooking structed of steel having a minimum thickness of 0.0296 inch
effluents as required by this section. Reduced vol- (0.7534 mm) (No. 22 gage) or stainless Slee! not less than
umes shall not be below that required to maintain cap- 0.0220 inch (0.5550 mm) (No. 24 gage) in thickness, copper
ture and removal of effluents from the idle cooking sheets weighing not less than 24 ounces per square foot (7 .3
appliances that are operating in a standby mode. kg/m 2) or of other approved material and gage.
507.2 Where required. A Type I or Type II hood shall be
507.6 Supports. Type I hoods shall be secured in place by non-
installed at or abo·.re all commercial cooking appliances in
combustible supports. All Type I and Type II hood supports
accordance with Sections 507.2.1 and 507.2 .2. Where any
shall be adequate for the applied load of the hood, the unsup-
cooking appliance under a single hood requires a Type I hood,
ported ductwork, the effluent loading and the possible weight
a Type I hood shall be installed. Where a Type II hood is
of personnel working in or on the hood.
required, a Type I or Type II hood shall be installed.
507.7 Hood joints, seams and penetrations. Hood joints,
507.2.1 Type I hoods. Type I hoods shall be installed where
seams and penetrations shall comply with Sections 507. 7.1 and
cooking appliances produce grease or smoke. Type I hoods
507.7.2.
shall be installed over medium-duty, heavy-duty and
extra-heavy-duty cooking appliances. Type I hoods shall be 507. 7.1 Type I hoods. External hood joints, seams and pen-
installed over light-duty cooking appliances that produce etrations for Type I hoods shall be made with a continuous
grease or smoke. external liquid-tight weld or braze to the lowest outermost
perimeter of the hood. Internal hood joints, seams, penetra-
507.2.1.l Operation. Type I hood systems shall be
tions, filter support frames and other appendages attached
designed and installed to automatically activate the
inside the hood shall not be required to be welded or brazed
exhaust fan whenever cooking operations occur. The
but shall be otherwise sealed to be grease tight.
activation of the exhaust fan shall occur through an inter-
lock with the cooking appliances, by means of heat sen- Exceptions:
sors or by means of other appmved methods.
1. Penetrations shall not be required to be welded or
I 507.2.2 Type II hoods. Type II hoods shall be installed
above dishwashers and light-duty appliances that produce
brazed where sealed by devices that are listed for
the application.
50 2009 INTERNATIONAL MECHANICAL CODE®
Page 7
EXHAUST SYSTEMS
2. Internal welding or brazing of seams, joints and arranged in place or provided with drip-intercepting devices
pe11etrations of the hood shall not be prohibited to prevent grease or other condensate from dripping into
provided that the joint is formed smooth or ground food or on food preparation surfaces.
so as to not trap grease, and is readily cleanable.
507.11.2 Mounting position. Filters shall be installed at an
507.7.2 Type II hoods. Joints, seams and penetrations for angle of not less than 45 degrees (O. 79 rad) from the hori-
Type II hoods shall be constructed as set forth in Chapter 6, zontal and shall be equipped with a drip tray beneath the
shall be sealed on the interior of the hood and shall provide a lower edge of the filters.
smooth surface that is readily cleanable and water tight.
507 .12 Canopy size and location. The inside lower edge of can-
507.8 Cleaning and grease gutters. A hood shall be designed opy-ty pe Type I and II commercial hoo?s shall overhang or
to provide for thorough cleaning of the entire hood. Grease gut- extend a horizontal distance of not less lhan 6 inches (152 mm)
ters shall drain to an approved collection receptacle that is fab- beyond the edge of the top horizontal surface of the appliance on
ricated, designed and installed to allow access for cleaning. all open sides. The vertical distance b tween the front lower lip
507.9 Clearances for Type I hood. A Type I hood shall be of the hood and such surface shall not exceed 4 feet (1219 mm).
installed with a clearance to combustibles of not less than 18
Exception: The hood shall be permitted to be flush with the
inches (457 mm).
outer edge of the cooking surface where the hood is closed
Exception: Clearance shall not be required from gypsum to the appliance side by a noncombustible wall or panel.
wallboard or 1/ 2-inch (12. 7 mm) or thicker cementitious
wallboard attached to noncombustible structures provided 507.13 Capacity of hoods. Commercial food service hoods
that a smooth, cleanable, nonabsorbent and noncombustible shall exhaust a minimum net quantity of air determined in
material is installed between the hood and the gypsum or accordance with this section and Sections 507 .13.l through
cementitious wallboard over an area extending not less than 507.13.4. The net quantity of exhaust airshall be calculated by
18 inches (457 mm) in all directions from the hood. subtracting any airflow supplied directly to a hood cavity from
the total exhaust flow rate of a hood. Where any combination of
507 .10 Hoods penetrating a ceiling. Type I hoods or portions heavy-duty. medium-duty and light-duty cooking appliances
thereof penetrating a ceiling, wall or furred space shall comply are utilized under a single hood, the exhaust rate required by
with all the requirements of Section 506.3.10. this section for the heaviest duty appliance covered by the hood
507.11 Grease filters. Type I hoods shall be equipped with shall be used for the entire hood.
listed grease filters designed for the specific purpose.
507.13.l Extra-heavy-duty cooking appliances. The min-1
Grease-collecting equipment shall be provided with access for imum net airflow for hoods, as determined by Section
cleaning. The lowest edge of a grease filter located above the 507.2, used for extra-heavy-duty cooking appliances shall
cooking surface shall be not less than the height spedfied in
be determined as follows:
Table 507.11 .
TABLE 507.11 Type of Hood CFM per linear foot of hood
MINIMUM DISTANCE BETWEEN THE LOWEST EDGE OF A Backshelf/pass-over Not allowed
GREASE FILTER AND THE COOKING SURFACE OR THE Double island canopy
HEATING SURFACE (per s ide) 550
Eyebrow Not allowed
TYPE OF COOKING
HEIGHT ABOVE
COOKING SURFACE
I Single island canopy 700
550
II Wall-mounted canopy
I
APPLIANCES
(feet)
For SI: 1 cfm per linear foot= 1.55 Us per linear meter.
'---
_ _, J
507.13.2 Heavy-duty cooking appliances. The minimum
Exposed flame and burners 2 net airflow for hoods, as determined by Section 507.2, used
l~!?.osed c~~c~al and charbroil type l._____3.5 for heavy-duty cooking appliances shall be determined as
follows:
For SI: I foot= 304.8 mm.
Type of Hood CFM per linear foot of hood
507.11.1 Criteria. Filters shall be of such size, type and Backs helf/pass-over 400
arrangement as will permit the required quantity of air to Double island canopy
pass through such units at rates not exceeding those for (per side) 400
which the filter or unit was designed or approved Filter Eyebrow Not allowed
units shall be installed in frames or holders so as to be Single island canopy 600
readily removable without the use of separate tools, unless Wall-mounted canopy 400
designed and installed to be cleaned in place and the system For SI: 1 cfm per linear foot= 1.55 Lis per linear meter.
is equipped for such cleaning in place. Removable filter
units shall be of a size that will allow them to be cleaned in a
dishwashing machine or pot sink. Filter units shall be
507.13.3 Medium-duty cooking appliances. The mini-
mum net airflow for hoods, as determined by Section 507.2,
I
2009 INTERNATIONAL MECHANICAL CODE® 51
Page 8
VENTILATION
SECTION 403 provide the flow rates as specified in Section 403.3. The
MECHANICAL VENTILATION required outdoor airflow rates specified in Table 403.3 shall
be introduced directly into such spaces or into the occupied
403. l Ventilation system. Mechanical ventilation shall be pro-
spaces from which air is transferred or a combination of
vided by a method of supply air and return or exhaust ail: The
amount of supply air shall be approximately equal to the both.
amount of return and exhaust air. The system shall not be pro- 403.3 Outdoor airflow rate. Ventilation systems shall be
hibited from producing negative or positive pressure. The sys- designed to have the capacity to supply the minimum outdoor
tem to convey ventilation air shall be designed and installed in airflow rate determined in accordance with this section. The
accordance with Chapter 6. occupant load utilized for design of the ventilation system shall
not be less than the number determined from the estimated
403.2 Outdoor air required. The minimum outdoor airflow
maximum occupant load rate indicated in Table 403.3. Ventila-
rate shall be determined in accordance with Section 403.3.
tion rates for occupancies not represented in Table 403.3 shall
Ventilation supply systems shall be designed to deliver the
be those for a listed occupancyclassification that is most simi-
required rate of outdoor airflow to the breathing zone within
lar in terms of occupant density, activities and building con-
each occupiable space.
struction; or shall be determined by an approved engineeting
Exception: Where the registered design professional dem- analysis. The ventilation system shall be designed to supply the
onstrates that an engineered ventilation system design will required rate of ventilation air continuously during the period
prevent the maximum concentration of contaminants from the building is occupied, except as otherwise stated in other
exceeding that obtainable by the rate of outdoor air ventila- provisions of the code.
tion determined in accordance with Section 403.3, the mini-
With the exception of smoking lounges, the ventilation rates
mum required rate of outdoor air shall be reduced in
in Table 403.3 are based on the absence of smoking in
accordance with such engineered system design.
occupiable spaces. Where smoking is anticipated in a space
403.2.1 Recirculation of air. The outdoor air required by other than a smoking lounge, the ventilation system serving the
Section 403.3 shall not be recirculated. Air in excess of that space shall be designed to provide ventilation over and above
required by Section 403.3 shall not be prohibited from being that required by Table 403.3 in accordance with accepted engi-
recirculated as a component of supply air to building spaces, neering practice.
except that: Exception: The occupant load is not required to be deter-
I. Ventilation air shall not be recirculated from one mined based on the estimated maximum occupant load rate
dwelling to another or to dissimilar occupancies. indicated in Table 403.3 where approved statistical data
document the accuracy of an alternate anticipated occupant
2. Supply air to a swimming pool and associated deck
density.
areas shall not be recirculated unless such air is dehu-
midified to maintain the relative humidity of the area 403.3.1 Zone outdoor airflow. The minimum outdoor air-
al 60 percent or less. Air from this area shall not be flow required to be supplied to each zone shall be deter-
recirculated to other spaces where more than I 0 per- mined as a function of occupancy classification and space
cent of the resulting supply airstream consists of air air distribution effectiveness in accordance with Sections
recirculated from these spaces. 403.3.1.1 through 403.3.1.3.
3. Where mechanical exhaust is required by Note bin 403.3.1.1 Breathing zone outdoor airflow. The outdoor
Table 403.3, recirculation of air from such spaces airflow rate required in the breathing zone (Vi,,) of the
shall be prohibited. All air supplied to such spaces occupiable space or spaces in a zone shal I be determined
shall be exhausted, including any air in excess of that in accordance with Equation 4-1.
required by Table 403.3.
Vb,= Rj>, + R,,A, (Equation 4-1)
4. Where mechanical exhaust is required by Note g in
Table 403.3, mechanical exhaust is required and where:
recirculation is prohibited where more than I 0 per- A, Zone floor area: the net occupiable floor area of
cent of the resulting supply airstream consists of air the space or spaces in the zone.
recirculated from these spaces.
P, Zone population: the number of people in the
403.2.2 Transfer air. Except where recirculation from such space or spaces in the zone.
spaces is prohibited by Table 403.3, air transferred from
occupiable spaces is not prohibited from serving as makeup RP People outdoor air rate: the outdoor airflow rate
air for required exhaust systems in such spaces as kitchens, required per person from Table 403.3.
baths, toilet rooms, elevators and smoking lounges. The R. Area outdoor air rate: the outdoor airflow rate
amount of transfer air and exhaust air shall be sufficient to required per unit area from Table 403.3 .
30 2009 INTERNATIONAL MECHANICAL CODE®
Page 9
VENTILATION
TABLE403.3
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
AIRFLOW RATE IN AIRFLOW RATE IN
BREATHING ZONE, RP BREATHING ZONE, R. DEFAULT OCCUPANT EXHAUST AIRFLOW
OCCUPANCY CLASSIFICATION CFM/PERSON CFM/FT28 DENSITY #11000 FT28 RATE CFM/FT28
Correctional facilities
Cells
without plumbing fixtures 5 0.12 25 -
with plumbing fixturess 5 0.12 25 1.0
Dining halls
(see food and beverage service) - - - -
Guard stations 5 0.06 15 -
Day room 5 0.06 30 -
Booking/waiting 7.5 0.06 50 -
Dry cleaners, laundries
Coin-operated dry cleaner 15 - 20 -
Coin-operated laundries 7.5 0.06 20 -
Commercial dry cleaner 30 - 30 -
Commercial laundry 25 - 10 -
Storage, pick up 7.5 0.12 30 -
Education
Auditoriums 5 0.06 150 -
Corridors (see public spaces) - - - -
Media center 10 0.12 25 -
Sports locker roomsB - - - 0.5
Music/theater/dance 10 0.06 35 -
Smoking loungesb 60 70 -
Day care (through age 4) 10 0.18 25 -
Classrooms (ages 5-8) 10 0.12 25 -
Classrooms (age 9 plus) 10 0.12 35 -
Lecture classroom 7.5 0.06 65 -
Lecture hall (fixed seats) 7.5 0.06 150 -
Art classrooms 10 0.18 20 0.7
Science laboratoriess 10 0.18 25 1.0
Wood/metal shopss 10 0.18 20 0.5
Computer lab 10 0.12 25 -
Multiuse assembly 7.5 0.06 100 -
Locker/dressing roomsB - - - 0.25
Food and beverage service
Bars, cocktail lounges 7.5 0.18 100 -
Cafeteria, fast food 7.5 0.18 100 -
Dining rooms 7.5 0.18 70 -
Kit hems {rsloking) b - - - 0.7
Hospitals, nursing and convalescent homes
Autopsy roomsb - - - 0.5
Medical procedure rooms 15 - 20 -
Operating rooms 30 - 20 -
Patient rooms 25 - 10 -
Physical therapy 15 - 20 -
Recovery and ICU 15 - 20 -
Hotels, motels, resorts and dormitories
Multipurpose assembly 5 0.06 120 -
Bathrooms/toilet-privates - - - 25/5or
Bedroom/living room 5 0.06 10 -
Conference/meeting 5 0.06 50 -
Dormitory sleeping areas 5 0.06 20 -
Gambling casinos 7.5 0.18 120 -
Lobbies/prefunction 7.5 0.06 30 -
(co11/inued}
2009 INTERNATIONAL MECHANICAL CODE® 31
Page 10
VENTILATION
TABLE 403.3-contlnued
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
AIRFLOW RA TE IN AIRFLOW RATE IN
BREATHING ZONE, RP BREATHING ZONE, R8 DEFAULT OCCUPANT EXHAUST AIRFLOW
OCCUPANCY CLASSIFICATION CFM/PERSON CFM/FT28 DENSITY #11000 Fr2 • RATE CFM/FT21
Offices
Conference rooms 5 0.06 50 -
Office spaces 5 0.06 5 -
Reception areas 5 0.06 30 -
Telephone/data entry 5 0.06 60 -
Main entry lobbies 5 0.06 10 -
Private dwellings, single and multiple
Garages, common for multiple unitsb - - - 0.75
Garages, separate for each dwellingb - - - 100 cfm per car
Kitchensb - - - 25/lQOf
Living areas< 0.35 ACH but not less - Based upon number of -
than 15 cfm/person bedrooms. First
bedroom, 2; each
additional bedroom, 1
Toilet rooms and bathroomsB - - - 20/50r
Public spaces
Con-idors - 0.06 - -
Elevator car - - - 1.0
Shower room (per shower head)8 - - - 5012or
Smoking loungesb 60 - 70 -
Toilet rooms - publicB - - - 50/70•
Places of religious worship 5 0.06 120 -
Courtrooms 5 0.06 70 -
Legislative chambers 5 0.06 50 -
Libraries 5 0.12 10 -
Museums (children's) 7.5 0.12 40 -
Museums/galleries 7.5 0.06 40 -
Retail stores, sales floors and
showroom floors
Sales (except as below) 7.5 0.12 15 -
Dressing rooms - - - 0.25
Mall common areas 7.5 0.06 40 -
Shipping and receiving - 0.12 - -
Smoking loungesb 60 - 70 -
Storage rooms - 0.1 2 - -
Warehouses (see storage) - - - -
Specialty shops
Automotive motor-fuel dispensing stationsb - - - 1.5
Barber 7.5 0.06 25 0.5
Beauty and nail salonsb· h 20 0.12 25 0.6
Embalming rnomb - - - 2.0
0.9
Pet shops (animal areas)b 7.5 0.18 10
Supermarkets 7.5 0.06 8 -
Sports and amusement
Disco/dance floors 20 0.06 100 -
Bowling alleys (seating areas) 10 0.12 40 -
Game arcades 7.5 0.18 20 -
Ice arenas without combustion engines - 0.30 - 0.5
Gym, stadium, arena (play area) - 0.30 - -
Spectalor areas 7.5 0.06 150 -
Swimming pools (pool and deck area) - 0.48 - -
Health club/aerobics room 20 0.06 40 -
Health club/weight room 20 0.06 10 -
(continued}
32 2009 INTERNATIONAL MECHANICAL CODE®
Page 11
VENTILATION
TABLE 403.3-contlnued
MINIMUM VENTILATION RATES
PEOPLE OUTDOOR AREA OUTDOOR
AIRFLOW RA TE IN AIRFLOW RATE IN
BREATHING ZONE, RP BREATHING ZONE, R8 DEFAULT OCCUPANT EXHAUST AIRFLOW
OCCUPANCY CLASSIFICATION CFM/PERSON CFM/FT28 DENSITY #11000 FT28 RATE CFM/FT2 "
Storage
Repair garages. enclosed parking garagesb,d - - - 0.75
Warehouses - 0.06 - -
Theaters
Auditoriums (see education) - - - -
Lobbies 5 0.06 150 -
Stages, studios 10 0.06 70 -
Ticket booths 5 0.06 60 -
Transportation
Platforms 7.5 0.06 100 -
Transportation waiting 7.5 0.06 100 -
Workrooms
Bank vaults/safe deposit 5 0.06 5 -
Darkrooms - - - 1.0
Copy, printing rooms 5 0.06 4 0.5
Meat processingc 15 - 10 -
Pharmacy (prep. area) 5 0.18 10 -
Photo studios 5 0.12 10 -
Computer (without printing) 5 0.06 4 -
For SI: I cubic foot per minute= 0.0004719 m 3/s, I ton= 908 kg, I cubic foot per minute per square foot= 0.00508m 3/(s · m 2),
C = [(F) -32]/l.8, I square foot= 0.0929 m2•
a. Based upon net occuplable floor area.
b. Mechanical exhaust required end the recirculation of air from such spaces Is prohibited (see Section 403.2. l, Item 3).
c. Spaces unheated or maintained below 50°F are not covered by these requirements unless the occupancy is continuous.
d. Ventilation systems in enclosed parking garages shall comply wlth Section 404.
e. Rates are per water closet or urinal. The higher rate shall be provided where periods of heavy use are expected to occur. such as toilets In theaters. schools and sports
facllltles. The lower rate shall be permitted where periods of heavy use are not expected.
f. Rates are per room unless otherwise Indicated. The higher rate shall be provided where the exhaust system Is designed to operate Intermittently. The lower rate shall
be permitted where the exhaust system is designed to operate continuously during normal hours of use.
g. Mechanical exhaust is required and recirculation ls prohibited except that recirculation shall be permitted where the resulting supply alrstream consists ofnot more
Ll1an I 0 percent air recirculated from these spaces (see Section 403.2. I, Items 2 and 4) .
h. For nail salons, the required exhaust shall include ventllatlon tables or other systems that capture the contaminants and odors at their source and are capable of
exhausting a minimum of 50 cfm per station.
2009 INTERNATIONAL MECHANICAL CODE® 33
Page 12
VENTILATION
403.3.1.2 Zone air distribution effectiveness. The zone outdoor air intake flow rate ( V r) shall be determined in
0
air distribution effectiveness (EJ shall be determined accordance with Sections 403. 3. 2. 3 .1 through
using Table 403.3.1.2. 403.3.2.3.4.
TABLE 403.3.1.2 403.3.2.3.1 Primary outdoor air fraction. The pri-
ZONE AIR DISTRIBUTION EFFECTIVENESS•·b,c,d,a
mary outdoor air fraction (Z) shall be determined for
Air Distribution Configuration E, each zone in accordance with Equation 4-5.
Ceiling or floor supply of cool air 1.0f
z = voz (Equation 4-5)
Ceiling or floor supply of warm air and floor return 1.0 p vpz
Ceiling supply of warm air and ceiling return 0.88
where:
Floor supply of warm air and ceiling return 0.7
~, = Primary airflow: The airflow rate supplied to
Makeup air drawn in on the opposite side of the room the zone from the air-handling unit at which
from the exhaust and/or return
0.8
the outdoor air intake is located. It includes
Makeup air drawn in near to the exhaust and/or return outdoor intake air and recirculated air from
location
0.5 that air-handling unit but does not include air
transferred or air recirculated to the zone by
For SI: I foot= 304.8 mm, I foot per minute = 0.00506 mis,
°C = [(°F) - 32]/J.8. other means. For design purposes, ~,shall be
a. "Cool air" is air cooler than space temperature. the zone design primary airflow rate, except
b. "Warm air" is air warmer than space temperature. for zones with variable air volume supply and
c. "Ceiling" includes any point above the breathing zone. ~, shall be the lowest expected primary air-
d. "Floor" includes any point below the breathing zone. flow rate to the zone when it is fully occupied.
e. "Makeup air" is air supplied or transferred to a zone to replace air removed
from the zone by exhaust or return systems. 403.3.2.3.2 System ventilation efficiency. The sys-
f. Zone air distribution effectiveness of 1.2 shall be permitted for systems with tem ventilation efficiency (E.) shall be determined
a floor supply of cool air and ceiling return, provided that low-velocity dis- using Table 403.3.2.3.2 or Appendix A of ASHRAE
placement ventilation achieves unidirectional flow and thermal stratifica-
tion. 62.1.
g. Zone air distribution effectiveness of 1.0 shall be permitted for systems with TABLE 403.3.2.3.2
a ceiling supply of warm air, provided that supply air temperature is less than SYSTEM VENTILATION EFFICIENCY•·b
15°F above space iemperature and pmv lded that Lhe 150 foot-per-minute
supply air jet reaches lo within 41/ 2 ff.el af floor lcv I. Max(Z,J Ev
403.3.1.3 Zone outdoor airflow. The zone outdoor air- :::; 0.15 1
flow rate ( V J, shall be determined in accordance with
0
Equation 4-2. :::; 0.25 0.9
:::; 0.35 0.8
voz = vbz
E, (Equation 4-2)
:::; 0.45 0.7
403.3.2 System outdoor airflow. The outdoor air required :::; 0.55 0.6
to be supplied by each ventilation system shall be deter- :::; 0.65 0.5
mined in accordance with Sections 403.3.2.1 through
403.3.2.3 as a function of system type and zone outdoor air- :::; 0.75 0.4
flow rates.
>0.75 0.3
403.3.2.1 Single zone systems. Where one air handler a. Max (Z) L~ Ille largest value of ZP calculated using Equation 4-5 among all
supplies a mixture of outdoor air and recirculated return the zones SPrvrd by the systr m.
air to only one zone, the system outdoor air intake flow b. Interpolating between table values shall be permitted.
rate ( V0 r) shall be determined in accordance with Equa-
403.3.2.3.3 Uncorrected outdoor air intake. The
tion 4-3.
uncorrected outdoor air intake flow rate ( V,,,) shall be
(Equation 4-3) determined in accordance with Equation 4-6.
403.3.2.2 100-percent outdoor air systems. Where one Vo,,= D"[,allzonesR~, + LallzonesR,,A, (Equation 4-6)
air handler supplies only outdoor air to one or more
zones, the system outdoor air intake flow rate ( V,,r) shall where:
be determined using Equation 4-4. D Occupant diversity: the ratio of the system
population to the sum of the zone populations,
(Equation 4-4)
determined in accordance with Equation 4-7.
403.3.2.3 Multiple zone recirculating systems. Where p
one air handler supplies a mixture of outdoor air and D= ~ (Equation 4-7)
recirculated return air to more than one zone, the system !: ull b>n"' ~
34 2009 INTERNATIONAL MECHANICAL CODE®
Page 13
VENTILATION
where: SECTION 405
SYSTEMS CONTROL
Ps = System population: The total number of occu-
pants in the area served by the system. For de- 405.1 General. Mechanical ventilation systems shall be pro-
sign purposes, P, shall be the maximum vided with manual or automatic controls that will operate such
number of occupants expected to be concur- systems whenever the spaces are occupied. Air-conditioning
rently in all zones served by the system. systems that supply required ventilation air shall be provided
with controls designed to automatically maintain the required
403.3.2.3.4 Outdoor air intake flow rate. The out- outdoor air supply rate during occupancy.
door air intake flow rate ( V0 ,) shall be determined in
accordance with Equation 4-8.
SECTION 406
v = VOi/ (Equation 4-8) VENTILATION OF UNINHABITED SPACES
ot Ev
406.1 General. Uninhabited spaces, such as crawl spaces and
403.4 Exhaust ventilation. Exhaust airflow rate shall be pro- attics, shall be provided with natural ventilation openings as
vided in accordance with the requirements In Table 403.3. required by the International Building Code or shall be pro-
Exhaust makeup air shall be permitted to be any combination vided with a mechanical exhaust and supply air system. The
of outdoor air, recirculated air and transfer air, except as limited mechanical exhaust rate shall be not less than 0.02 cfm per
in accordance with Section 403.2. square foot (0.00001 m3/s. m2) of horizontal area and shall be
automatically controlled to operate when the relative humidity
403.5 System operation. The minimum flow rate of outdoor in the space served exceeds 60 percent.
air that the ventilation system must be capable of supplying
during its operation shall be permitted to be based on the rate
per person indicated in Table 403.3 and the actual number of
occupants present.
403.6 Variable air volume system control. Variable air vol-
ume air distribution systems, other than those designed to sup-
ply only 100-percent outdoor air, shall be provided with
controls to regulate the flow of outdoor air. Such control system
shall be designed to maintain the flow rate of outdoor air at a
rate of not less than that required by Section 403.3 over the
entire range of supply air operating rates.
403.7 Balancing. The ventilation air distribution system shall
be provided with means to adjust the system to achieve at least
the minimum ventilation airflow rate as required by Sections
403.3 and 403.4. Ventilation systems shall be balanced by an
appmved method. Such balancing shall verify that the ventila-
tion system is capable of supplying and exhausting the airflow
rates required by Sections 403.3 and 403.4.
SECTION 404
ENCLOSED PARKING GARAGES
404. t Enclosed parking garages. Mechanical ventilation
systems for enclosed parking garages shall be permitted to
operate intermittently where the system is arranged to operate
automatically upon detection of vehicle operation or the pres-
ence of occupants by appmved automatic detection devices.
404.2 Minimum ventilation. Automatic operation of the sys-
tem shall not reduce the ventilation airflow rate below 0.05 cfm
per square foot (0.00025 m3/s · m2) of the floor area and the sys-
1
tem shall be capable of producing a ventilation airflow rate of
0.75 cfm per square foot (0.0038 m 3/s · m 2) of floor area.
404.3 Occupied spaces accessory to public garages. Con-
necting offices, waiting rooms, ticket booths and similar uses
that are accessory to a public garage shall be maintained at a
positive pressure and shall be provided with ventilation In
accordance with Section 403.3.
2009 INTERNATIONAL MECHANICAL CODE® 36