1. Unit 1 Turbine Steam Seal Repair - McKee Run Generating Station
2. Updates
A. National Pollution Discharge Elimination System (NPDES) Municipal Separate Storm
Sewer Systems (MS4) Permit
B. Garrison Oak Technical Park Project
3. Adjournment by 5:55 P.M.
/tm
S:\AGENDAS-MINUTES-PACKETS\Committee-Agendas\2012\10-08-2012 UTILITY.wpd
THE AGENDA ITEMS AS LISTED MAY NOT BE CONSIDERED IN SEQUENCE. THIS AGENDA IS SUBJECT TO CHANGE TO
INCLUDE THE ADDITION OR THE DELETION OF ITEMS, INCLUDING EXECUTIVE SESSIONS.
Page 2
ACTION FORM
PROCEEDING: Utility Commitee
DEPARTMENT OF ORIGIN: Public Utilities- Power Plant (NAES) DATE SUBMITTED: 10/8/12
PREPARED BY: Vincent Scire, Plant Manager
SUBJECT: NEW CIP - Unit 1 Turbine Steam Seal Repair - McKee Run Generating Station
REFERENCE: N/A
RELATED PROJECT: N/A
REVIEWED BY: City Manager & Controller/Treasurer
EXHIBITS: New CIP- Unit 1 Turbine Steam Seal Repair
EXPENDITURE REQUIRED: $65,000.00 AMOUNT BUDGETED: $ -0-
FUNDING SOURCE (Dept./Page in CIP & Budget): Electric Improvement & Extension Fund carry forward balance
TIMETABLE: This work is scheduled to be completed in November, 2012 during a planned maintenance outage on Unit 1
RECOMMENDED ACTION: Staff recommends approving the new CIP and the expenditure of funds in fiscal 2013
BACKGROUND AND ANALYSIS
McKee Run Unit 1 steam turbine developed a steam leak on the governor end of the machine. This leak has
progressively gotten worse to the point that it is affecting the operation of the #1 bearing on this unit. When
operating, this bearing is now running at elevated temperatures when the unit is at full load. This is an
undesirable condition which could lead to damage to the bearing (if it is not already damaged), and possibly
result in a forced outage. This Unit is not likely to operate until the spring of 2013; however, repairs need to be
made as soon as possible to avoid further damage to the unit.
To address the problem we will replace the governor end outer gland seals and inspect the #1 bearing for
damage. This will require:
Removing the outer gland housing and seals
Send seals to the OEM for refurbishment
Reinstall the seals and gland housing, Align the housing to the turbine shell,
Remove the governor table to access the #1 bearing
Remove the bearing and inspect/ repair as necessary, reassemble the bearing. If work on the bearing
is required, an alignment check will have to be performed.
Reassembly of the governor table
Operationally test the unit.
The cost to perform this work is $65,000 assuming no damage is found to the #1 bearing. The work can easily
be accomplished in the fall outage timeframe. However, this work was not included in the original 2013 O&M
budget nor in the 2013 CIP budget.
Page 3
Capital Investments Plan FY 13 thru FY 17
City of Dover, Delaware
Project #: EG1301
Project Name: McKee Run Unit 1 Turbine Steam Seal Repairs
Type: Maintenance Department: Public Utilities-Power Plant
Useful Life: Unknown Contact: Power Plant Manager
Category: Electric Priority: 1
New Project: YES Account #: 487-8101-591.40-89
Time-Line: Work to be complete in
November 2012
Total Project Cost: $65,000
Description
McKee Run Unit 1 steam turbine developed a steam leak on the governor end of the machine. This leak has progressively gotten worse
to the point that it is affecting the operation of the #1 bearing on this unit. When operating, this bearing is now running at elevated
temperatures when the unit is at full load. This is an undesirable condition which could lead to damage to the bearing (if it is not already
damaged), and possibly result in a forced outage. This Unit is not likely to operate until the spring of 2013, However, repairs need to be
made as soon as possible to avoid further damage to the unit and potential effects on unit capacity.
To address the problem we will replace the governor end outer gland seals and inspect the #1 bearing for damage. This will require:
Removing the outer gland housing and seals
Send seals to the OEM for refurbishment
Reinstall the seals and gland housing, Align the housing to the turbine shell,
Remove the governor table to access the #1 bearing
Remove the bearing and inspect/ repair as necessary, reassemble the bearing. If work on the bearing is required, an
alignment check will have to be performed.
Reassembly of the governor table
Operationally test the unit.
Justification
This work is required to maintain the turbine reliability. Delaying this work will result in further damage to the unit and /or reduced capacity on the
Unit. The consequence of this damage could result in an extended forced outage and subsequently impact capacity and generation revenues for
the Utility.
Prior Expenditure FY 13 FY 14 FY 15 FY 16 FY 17 Total Future
Construction/Maintenance $65,000 $65,000
Total Other
Miscellaneous
Total $65,000 $65,000
Prior Funding Sources FY 13 FY 14 FY 15 FY 16 FY 17 Total
Electric I & E Fund
Total Total $65,000 $65,000